Problem
Pilot light will not stay lit
A pilot that lights and dies as soon as you release the control is the classic thermocouple or thermopile failure, but the cause can also be a weak pilot flame, a draught, or the gas control itself. This page explains the sensing circuit, what to check, and when relighting becomes unsafe.
If you smell gas
- Stop what you are doing. Do not use phones, switches, matches or anything that can spark inside.
- Go outside and leave the door open behind you.
- Call the FortisBC 24-hour emergency line at 1-800-663-9911 or dial 911.
Only after that, call CANRO about the water heater. Official guidance: FortisBC gas leaks and odour.
The part that holds the pilot on
On a standing-pilot gas tank, the pilot's job is to keep the gas valve open through a thermocouple or thermopile: the pilot flame heats the sensor, the sensor generates a small voltage, and that voltage holds the safety valve open. Release the control knob and the pilot dies when the sensor cannot produce enough voltage, which is why a pilot that will not stay lit usually means the sensor, its flame, or the valve.
The distinction matters for the fix: a thermocouple that fails slowly may hold for minutes then drop out, while a weak or misaligned pilot flame never heats the sensor properly in the first place. Both look identical from the shower: no hot water, pilot out.
What the checks are
The technician's checks run in order: the pilot flame must be steady and must envelop the sensor tip; the sensor's millivolt output must meet the control's requirement; the connections at the control must be clean and tight; and the control itself must hold the valve once the voltage is good. Bradford White's service manual documents the thermocouple and thermopile tests and the pilot assembly service procedures behind these checks.
A draught through the burner compartment, a dirty pilot orifice, or a gas-pressure problem can each starve or disturb the pilot flame and produce the same symptom, which is why the flame is inspected before parts are replaced.
The relight trap
Relighting a pilot that will not stay lit is the most repeated homeowner action in water-heater service, and it is harmless only if the cause is understood. If the pilot dies the instant the button is released, the cause is the sensing circuit and relighting will not help. If gas smell appears at any point, stop and treat it as a leak: leave and call FortisBC or 911.
Frequently asked questions
Is the thermocouple the same as the thermopile?
Both are pilot-flame sensors that generate voltage. A thermocouple drives a simple safety valve; a thermopile generates more power and also runs millivolt controls and, on electronic units, powers the control circuit. The manual for the tank identifies which is fitted.
How long does a thermocouple last?
They age and fail like any part; there is no reliable calendar. The symptom is the test: a pilot that will not stay lit with a clean, steady flame points at the sensor or valve, confirmed by the millivolt reading.
Can I replace the thermocouple myself?
It is a gas-train part: replacement involves the gas control and is licensed-gas-fitter work in BC. The diagnostic visit prices it with the fee credited toward the repair.
Talk to a water heater technician
Describe what the water heater is doing and get a straight answer about the next step.
On-site service in Metro Vancouver, BC. Call to check availability.
Sources and verification
- CANRO Heating & Cooling — About · Canadian source · accessed September 7, 2026
- FortisBC — gas leaks and odour · Canadian source · accessed September 7, 2026
- Bradford White Defender Service Manual (thermocouple and thermopile tests) · 238-51542-00E · accessed September 7, 2026
Facts checked September 7, 2026. Last updated September 7, 2026. Technical reviewer: not yet assigned.